The key to network distance is Optical Power Budget: the amount of
light available to make a fiber optic connection. This paper will explain
how to determine the maximum fiber optic distances attainable using
media converters in various network environments. A simple calculation
is used to determine how much fiber optic light, measured in "dBms",
is available. The first step in calculating the Optical Power Budget is determining
how much light is available for the electronic devices themselves. Two
measurements are needed from the manufacturer of the equipment. Minimum
transmit power represents the worst case transmit power for a device
- the device is guaranteed to provide at least that much power. Please
note that some vendors will list an "average minimum transmit power".
Average minimum transmit power does not guarantee that a product will
perform at that products' minimum transmit power. Use caution when purchasing
products based on the averages. 
The second piece of information required is the minimum receive sensitivity.
This figure represents the minimum amount of light required by the receiver
to operate correctly. Again, the actual minimum should be used, not
an average of minimums. With minimum transmit power and minimum receive sensitivity data, we
can now calculate the available light. To accomplish this, simply subtract
the minimum receive sensitivity from the minimum transmit power (available
light = minimum transmit power - minimum receive sensitivity). Note
that the minimum receive sensitivity is usually a negative number such
as -33dBm. Subtracting a negative number is the same as adding its absolute
value. For example, if a device has a minimum transmit power of -10dBm
and a minimum receive sensitivity of -33dBm, the available power will
be -10dB - (-)33dB = 23dB or -10B + 33dB = 23db. | TIA standard for connector loss | .75 dB | | Typical cable attenuation at 1310nm | .4 dB | | Typical cable attenuation at 1550nm | .3 dB | | Typical splice attenuation | .1 dB | | Typical distance between splices | 6 km | | Typical safety margin | 3 dB |
Also, when connecting devices from different vendors,or different
models of products from the same vendor, the available power calculation
needs to be computed in both directions with the smaller of the two
used for the rest of the calculations. For example, assume you are connecting
two devices labeled "Device" 1 and Device 2. Device 1 has a minimum
transmit power of -3dBm and a minimum receive sensitivity of -32dBm
and Device 2 has a minimum transmit power of -1dBm and a receive sensitivity
of -31dBm. The available power going from Device 1 to Device 2 would
be calculated by -3dBm - (-)31dBm or 28dB. The available power going
from Device 2 to Device 1 would be calculated by -1dBm - (-)32dBm or
29dB. There is less light available in the Device 1 to Device 2 direction
so we will use that figure for our calculations, if that half of the
link works then so will the other. From available power we must subtract out all of the losses. These
losses include cable attenuation, connector loss, and splice loss. Cable
attenuation is often the most significant loss factor. Cable attenuation
is determined by getting the exact number off of the cable you are installing,
or using the manufactures worst case number of the type of fiber you
planned to install. This number will range from .22dB to .5dB per kilometer.
Multiply this factor by the number of kilometers in the installation.
A fiber with .4db per kilometer of loss will loose 16db over a 40km
distance. Also remember that fiber does not come in 40km spools, therefore a
40km installation will have several splices. Each splice will typically
introduce .1db of additional loss. The fiber installers should be able
to provide a guaranteed worst case number. Multiply this number by the
number of splices. Connectors are another source of light loss. A typical long haul installation
will have six connectors in the installation. The first connects the
fiber to electronics. This connector is usually on indoor, plenum rated
fiber. This fiber connects the equipment room to the building entrance
for the outdoor (buried or aerial) fiber. There is another connector
on this end of the indoor cable and one on the outdoor cable. This is
repeated at the other end of the network for a total of six connectors.
Individual networks can vary however, and the exact number must be determined.
Connector loss is provided by the connector manufacturer and the installer.
Multiply the number of connectors by the loss for each connector to
get total connector loss. Each of these losses, cable attenuation, connector loss, and splice
loss is then subtracted from the available power. If this number is
negative, there is no need to continue, as there is not enough power
to drive the network. If this number is positive, there are two more
things to consider before pronouncing the network fit. The first is
what happens if the fiber gets cut and I have to splice it back together?
A proper installation will count on this happening and account for it
in the power budget. An estimation of the number of anticipated repairs
over the life of the fiber needs to be made. These repairs will add
splice loss, so we must multiply the number of anticipated splices by
the loss of each splice (same number we used above), and subtract this
from the remaining power. The number should still be positive. Finally, you must account for temperature extremes, as well as any
other unforeseen factors. This is typically done by determining a "safety
factor". This number will be different for every organization depending
on how much risk they want to assume in their network. Typically a value
around 3dB is used. To guarantee error free operation, a value no less
then 1.7dB should be used. This safety factor is subtracted from the
remaining power from above. If the number is still positive after all
of this, you can be assured that your fiber network will deliver the
required performance over the life of the installation.
The table to the right contains some typical
numbers, which can be used to approximate optical link budget calculations.
If at all possible, real numbers from the network in question should
be used.
(back to top)
|